STEP 4 – ELECTRICAL – (Continued) – High Voltage and Field Control Wiring
The following illustration provides an example of control wiring connections when using a standard thermostat.
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is
located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.

TYPICAL CONTROL WIRING

Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
A - Run 24VAC control wires through hole with grommet.
B - Make 24VAC thermostat wire connections to CMC1.
WIRE RUN LENGTH
LESS THAN 100' (30 METERS)
MORE THAN 100' (30 METERS) 16
HIGH VOLTAGE
FIELD WIRING
Low Voltage Wiring
Thermostat
R
POWER
C
COMMON
W1
1ST. STAGE AUX.
HEAT
G
INDOOR BLOWER
O
Y1
(SOME CONNECTIONS MAY NOT APPLY. REFER
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
NOTE - Wire tie provides low voltage wire strain relief and maintains separation of field-installed low and high voltage circuits.
STEP 5 – UNIT START-UP
IMPORTANT
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
1 - Rotate fan to check for binding.
2 - Inspect all factory- and field-installed wiring for
loose connections.
3 - After evacuation is complete, open the liquid line
and vapor line service valve stems to release the
refrigerant charge (contained in outdoor unit) into
the system.
4 - Replace the stem caps and tighten to the value
listed in table 2.
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until
you have consulted with the power company and
ROUTING HIGH VOLTAGE, GROUND AND CONTROL WIRING
AWG# INSULATION TYPE
18
TEMPERATURE RATING
35ºC MINIMUM.
LOW VOLTAGE
FACTORY
FIELD WIRING
WIRING
Outdoor Unit
Indoor Unit
R
POWER
C
COMMON
W1
1ST. STAGE AUX.
HEAT
W2
W3
G
REVERSING VALVE
COMPRESSOR
NOTE - Do not bundle any excess 24VAC control wires inside control panel.
NOTE - For proper voltages, select thermostat wire (control wires) gauge per
table below.
Low Voltage Wiring (with Auxiliary Heat)
Thermostat
R
POWER
C
COMMON
E
EMERGENCY
HEAT
R
W1
C
1ST. STAGE AUX.
HEAT
W1
G
INDOOR BLOWER
O
Y1
O
(SOME CONNECTIONS MAY NOT APPLY. REFER TO
Y1
SPECIFIC THERMOSTAT AND INDOOR UNIT.)
FIGURE 11
the voltage condition has been corrected.
6 - Connect manifold gauge set for testing and
charging.
7 - Set the thermostat for a cooling demand. Turn
on power to the indoor indoor unit and close the
outdoor unit disconnect switch to start the unit.
8 - Recheck voltage while the unit is running. Power
must be within range shown on the unit nameplate.
9 - Check system for sufficient refrigerant using the
procedures outlined under Checking Refrigerant
Charge.
OPERATING MANIFOLD GAUGE SET AND SERVICE
VALVES
The liquid and vapor line service valves are used for re-
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a
factory-installed valve stem. Figures 15 and 16 provide
information on how to access and operate both angle- and
ball-type service valves.
Page 11