CP Electronics MWS5 제품 설명서 - 페이지 10

{카테고리_이름} CP Electronics MWS5에 대한 제품 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. CP Electronics MWS5 12 페이지. Miniature ceiling mounted microwave presence detector

5. Programming (continued)
4
Dimming Channel 2 functions -DD & -AD only (factory default in brackets):
4.1
Light level
4.2
Presence detection
(default)
4.3
Absence detection
4.4
Switch level on (9)
4.5
Switch level off (9)
4.6
DSI (default)
4.7
DALI
4.8
Memorise (N)
4.9
On value (99)
4.10 Off value (0)
4.11 Fade value (10)
4.12 Fade mins (0)
4.13 Max value (99)
4.14 Min value (1)
4.15 Speed on (40)
4.16 Speed set (5)
4.17 Set seconds (120)
5

User Menu

DD-LCDHS user menu or UHS handset functions:
5.1
Lux up
5.2
Lux down
5.3
Scene up
5.4
Scene down
5.5
Scene#
5.6
Override on
5.7
Override off
5.8
Cancel
5.9
Set
page 10
Maintained illuminance level (adjustable between 1 and 999). At 999 the
output will be always be at maximum.
Auto switch on with detection, auto off after movement ceases and
time delay ends.
Manual switch on, auto off after movement ceases and time delay ends.
Lux level setting to prevent the luminaires being switched on if the
ambient light level is sufficient (adjustable between 1 and 9). The
luminaires will always be switched on at level 9.
Lux level setting to switch the luminaires off during occupancy if the
ambient light level goes above the setting (adjustable between 1 and 9).
Level 9 will always keep the lights on. This setting can be used for
―window row switching‖.
Selects DSI dimming (not applicable on EBMPIR-AD)
Selects DALI dimming (not applicable on EBMPIR-AD)
If this is set to Yes, the last manual lux level set will be memorised and
used as the new switch on level.
Dimming output level when switched on (0-99).
Dimming output level when switched off (0-99). If set to anything other
than 0 the light will not switch off but maintain a background lighting level.
After occupancy ceases, this dimming output level is loaded for the fade
time (adjustable between 0 and 99).
This is the time period (adjustable between 0 and 99 minutes) that the
luminaire will be held at the fade value before turning off. A value of 0
disables the fade function.
Maximum dimming output level (adjustable between 0 and 99).
Minimum dimming output level (adjustable between 0 and 99).
Determines the dimming response speed after the setup time has
finished. Measured in 0.1 sec intervals.
Determines the dimming response speed during the set up time.
Measured in 0.1 sec intervals.
Determines how long the dimming response set-up period lasts on power-
up or on setting change (adjustable between 1 and 999 seconds). This
enables the desired lux level to be achieved rapidly when the lights come
on, or during setup.
Increase light level. Reverts when occupancy cycle complete.
Decrease light level. Reverts when occupancy cycle complete.
Steps up between 6 pre-defined scenes.
Steps down between 6 pre-defined scenes.
Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%;
3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)
Permanently overrides the luminaire output on.
Permanently overrides the luminaire output off.
Cancels the on or off override, returning the detector to normal operation.
If sent before using lux up or lux down, it will set the light level as in 4.1