Advanced programming
Parameter Name
Default Value
Detector Parameters
Walk Test LED
Off
Time Out
20 minutes
(Time adjustment)
Manual Time Out
10 minutes
Sensitivity On
9
Sensitivity Off
9
Lux time
0
Power Up State
On
Inhibit
4 seconds
Factory default
-
Switching functions
Lux on level
9
(Switch level on)
Lux off level
9
(Switch level off)
User Modes
Override On
-
Override Off
-
-
Cancel
6
Range / Options
Description
On or Off
When set to On this causes a red LED to flash on the sensor when it detects
movement. Use this feature to check for adequate sensitivity levels.
0-99 minutes
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay – use for commissioning only.
0-99 minutes
When a manual operation occurs, either via the switch input or the infrared, it
invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and
a manual timeout of 3 minutes. When the user leaves the room they press the off
button. The sensor will revert to automatic after 3 minutes, and then walking back
in the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a
presentation) but stays in the room. Every time a movement is detected, the
manual timeout period is re-triggered, but when it doesn't pick up for the short
timeout period, the sensor will timeout and revert to automatic. This means the
lights may turn on inadvertently during the presentation, if the occupants are still
for the manual timeout period, so adjust the timing carefully.
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
Sensitivity On and Off to the same value.
0 (disabled)
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
1-99 minutes
timed delay the lux change reverses then the process is cancelled.
On or Off
Select No for a 30 second delay on start up. If Yes is selected, there will be no
delay on start up and the detector will always power up detecting.
When the detector turns off, a delay is instigated to prevent retriggering. In certain
1 to 999 seconds
circumstances this delay may not be enough. This parameter allows the delay to
be changed.
-
Restores factory default settings
1 to 9
Sets a minimum light level below which the Microwave sensor is enabled, allowing
lights to be turned on by movement.
For a higher
Note: the Lux Level Off value must always be greater than the Lux Level On value.
resolution a scale
of 101-199 is
available
1 to 9
Sets a maximum light level above which the Microwave sensor is disabled,
preventing lights from being turned on by movement.
For a higher
resolution a scale
of 101-199 is
available
-
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period .
-
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
-
Cancels the on or off override, returning the detector to normal operation.
✓
✓
✓
✓
✓
✓*
✓
✓*
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓