UNLCDHS Programming – Output Ch. 2
Advance Parameters available for EBDHS-B01-DD
Parameter
On Value
Off Value
Burn-in Hours
Speed (On)
Speed (Setup)
Set Seconds
UNLCDHS Programming – Device information
Under the device Info menu are items about the device that can be read back to the handset.
Note: Not all devices support any or all of the information below.
• Range: e.g Standalone
• Part number: e.g MWS6
• Variant: e.g DD, PRM output variants
• Version: Version of software of the device.
Default
Range / Option
99
0 – 99
0
0 – 99
0
1 – 999 hours
(0 = disabled)
40
0 – 99 seconds
5
0 – 99
120
0 – 999 seconds
Dimmed output level when lights manually switched on or via detection of
occupancy.
Dimmed output level when lights manually switched off or after detector
times out.
Determines how long the output will be at 100% so that new lamps burn-in.
The burn-in time is not affected by power supply interruptions.
Determines the dimming response speed during the set up time upon power
ON. Measured in 0.1 sec intervals.
If set to "0" will disable dimming for Set Seconds below, used if fittings are
required to warm up before dimming.
Determines how long the dimming response set-up period lasts upon power-
up or on setting change. This enables a faster set up time.
Sets the dimming response speed after the setup time has finished.
Measured in 0.1 sec intervals (i.e. a value of 40 means 4 seconds).
Description