LIGHTS DO NOT COME ON
Check to see if the live supply to the circuit is
good. Strap across the L and LIVE OUT termi-
nal to turn the load on.
LIGHTS DO NOT GO OFF
Ensure that you have waited for the time out
period.
If the lights still do not go off then it is likely the
unit was not given the 20 seconds start up pe-
riod on installation. Follow this procedure:
1.
Isolate the mains supply to the circuit at
the main consumer unit and unscrew
the unit from the wall.
2.
Push the override switch to the off posi-
tion.
3.
Reapply the mains and wait for 20 sec-
onds.
4.
Activate timer as normal.
LIGHTS FLICKER
Ensure that there are sufficient power factor
correction capacitors fitted.
P
N
ART
UMBERS
ELLIPSE
Electronic time lag switch push button activated
KH2
Electronic time lag switch touch activated
ELLIPSE/TN
Electronic time lag switch push button activated with neon
KH2N
Electronic time lag switch touch activated with neon
IMPORTANT NOTICE!
This device should be installed by a qualified electrician
in accordance with the latest edition of the IEE wiring
regulations.
S
PECIFICATION
LOAD
10A of lighting including incandescent, fluorescent, compact fluorescent, low voltage (switch
primary of transformer).
Fluorescent and compact fluorescent fittings with "switch start" ballasts - 10 ballasts maximum.
Power factor correction capacitors must be fitted.
Most fluorescent fittings have power factor correction capacitors fitted. If they are not present
the unit may fail to turn off properly or flicker. In this case fit one capacitor per circuit with a
minimum value of 1μF for every unit installed. The capacitor should be fitted across switched
live and neutral. Note that it is not necessary to fit a capacitor on every fitting. This also applies
to fittings controlled with high frequency ballasts and maintained emergency fittings.
Not suitable for switching contactors
Not suitable for SON lighting
Not suitable for heating or ventilation loads.
Please contact our sales department for a suitable alternative product.
220-240 Volts AC 50 Hz
SUPPLY VOLTAGE
20 seconds to 20 minutes (approximate)
TIME OUT PERIOD
Surface fixing 25mm deep plastic surface mount moulded box.
FIXING METHOD
Flush fixing
TERMINAL CAPACITY 1.5mm
Flame retardant ABS
MATERIAL
Class 2
TYPE
-10°C to 35°C
TEMPERATURE
EMC-89/336/EEC
CONFORMITY
LVD-73/23/EEC
Due to our policy of continual
p r o d u c t
i m p r o v e m e n t
Electronics reserves the right to
alter
the
specification
of
product without prior notice.
25mm steel wall box or 32mm deep cavity wall box.