Parameter Name
Default Value
Individual Input Channel - continued
Local Off Scene /
20
Level
Local On Time
255
Local Step Time
255
Local On Rate
2 seconds
Local Off Rate
2 seconds
Scene raise / lower
6 seconds
rate
Toggle at input
No
Circuit Number
1
Sequence Number
1
Device config menu
RF Enabled
+Rx+Tx
IR Enabled
Yes
RF Channel
2
RF Tx Power
3
Discovery Declare
Soft Reset
Factory Reset
Deep sleep
0
Advanced programming (UNLCDHS)
Range / options
1 to 220
1 to 20 will select local OFF scene.
101 to 220 will select Area OFF
scene
0 to 255
0 – Ignore the on scene
1 to 59 – 1 to 59 in 1 second
increments.
60 to 177 – 1 to 59.5 minutes in 05
minutes increment.
178 to 254 – 1 to 20 hours in 15mins
increment.
255 – Infinite timeout.
0 to 255
0 to 255
0 – instant
1 to 59 – 1 to 59 in 1 second
increments.
60 to 177 – 1 to 59.5 minutes in 0.5
minutes increment.
178 to 254 – 1 to 20 hours in 15mins
increment.
255 – Infinite
0 to 255
0 to 255 seconds
Yes/No
0 to 999
0 to 999
+Rx+Tx
-Rx+Tx
+Rx-Tx
-Rx-Tx
Yes/No
0, 1 or 2
1 to 7
Value doesn't matter
0 - disabled
1 - enabled
Description
The local scene that is activated to turn the lights off. (says area
scene in UNLCDHS help)
This is common On Time parameter between Input function ON/OFF
Scene Recall, ON/OFF Circuit Absolute, Start/Stop Emergency.
Same as Local On time for scene and circuit modes.
This is common parameter between input functions depending on
which is enabled. It is common between scene recall, scene raise/
lower, On at last scene, On at last manual scene
On at last level,
Circuit On/Off
Circuit raise/lower.
Fade at end of step time to off scene.
This is common parameter between functions scene recall On/Off,
Circuit On/Off, scene raise/lower.
Enable/disable toggling at the input (eg single-button system).
Toggles between Set1 and Set2 parameters. This is used in Preset 2
and 12 for toggle function.
Sets the circuit number for the corresponding input switch function
below.
On at last level
On circuit absolute
Off circuit absolute
Circuit raise
Circuit lower
Configure the sequence number to be active.
Enable / disable radio communication between units.
Once IR reception is disabled, the only IR command that works is this
one to allow re-enabling. Prevents device from responding to IR.
868MHz band radio channels 1G1, 1G2, 1G3with different duty cycle
restrictions
0=-20dBm, 1=-10dBm, 2=-5dBm, 3=0dBm, 4=+3dBm, 5=+5dBm,
6=+8dBm, 7=+10dBm
Send a requested Discovery Declare Presence message and stay
awake.
Start the processing from scratch, clearing temporary variables, but
no loss of configs.
Restores factory default settings, also called hard reset. An-10
products require the device code.