CPS TEMP-SEEKER TM360C 소유자 매뉴얼 - 페이지 13

{카테고리_이름} CPS TEMP-SEEKER TM360C에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. CPS TEMP-SEEKER TM360C 20 페이지. Precision thermo-psychrometer multi-channel air conditioning humidity and temperature drop tester

STANDARD OT & TXV SYSTEM TEST
Refer to figure D-1, Below 
Hook up TMX3C Clamp-on probe or TMX2S Velcro Strap-On temp probes as
follows: Channel A to inlet and channel B to outlet of evaporator*/condenser (*use
optional TMX2FP Flex Surface Probe on evaporator inlet for vehicles like GM S-10
and Ford Trucks where orifice tubes are mounted at the evaporator inlet). 
Hook up either TMX2A Moving Air probe or TMX2GA General Purpose Air probe
from channel C to monitor ambient temperature 1-2' in front of the condenser. 
Hook up a second air probe from channel D to check vent air temperature in the
vent closest to the evaporator
Hook a RH (Relative Humidity) probe to the AUX port. Vent temperatures will
increase significantly as humidity levels rise, so this will allow you to follow the
OEM specifications for minimum vent temps based upon ambient air temp and
RH level.
Figure D-1

VARIABLE DISPLACEMENT COMPRESSORS

The compressor control valve may mask a refrigerant undercharge when checking
max heat load in the service bay. The recommended practice is to assure that the
compressor is commanded to a 100% duty cycle during testing. Various methods are
available to perform this function.
13