Avtec TAKU Premier Ventilation 운영자 매뉴얼 - 페이지 12
{카테고리_이름} Avtec TAKU Premier Ventilation에 대한 운영자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Avtec TAKU Premier Ventilation 12 페이지. Premier ventilation
MAKE-UP AIR HOODS
1055 Mendell Davis Drive
1. Close all doors and windows.
2. Operate all exhaust fans even those serving other hoods, supply fans, make-up air
unit and building HVAC system.
3. Turn on all cooking equipment under the hood and preheat to operating temperature.
4. Produce large quantities of smoke or steam.
5. Observe capture of vapors.
6. If all vapors are not totally captured, ne tune the system by adjusting the air volume
control damper installed in the supply collar. Slightly reduce the amount of supply air
directed under the hood until full capture is obtained.
UNIFIED BRANDS
Jackson, MS 39272
888-994-7636
Final Air Balance
fax 888-864-7636 unifiedbrands.net