Avtech TMP-SDT-SEN 설치 참고 사항 - 페이지 4
{카테고리_이름} Avtech TMP-SDT-SEN에 대한 설치 참고 사항을 온라인으로 검색하거나 PDF를 다운로드하세요. Avtech TMP-SDT-SEN 5 페이지. Difgital temperature & analog sensor
Digital Temperature & Analog Sensor (RMA-DTA-SEN)
• In "Units," enter a 1 to 3 character label for the unit type that your readings will
be measured in. If you are measuring amperage (A), you might enter "A" or
"Amp," as we have in the above example. Note that this field is merely a label
and does not affect any of the calculations.
5. Next, fill in the set of fields to the left of the screen:
• In "Sensor Label," you may leave the default "Ext Sensor 1" or enter a descriptive
name of up to 15 alphanumeric characters, such as "T/A Server AC" or "Rack 1 Fan
T/A."
• In "Alarm On," you may leave the "High" and "Low" for both "Temperature" and
"Analog," at the default, 0—which means no alarm is configured—or enter values of
up to 4 characters. Your monitor generates alerts based on those thresholds.
o Temperature: Enter values according to the default temperature scale (Fahrenheit
or Celsius). Please refer to your Room Alert or TemPageR User's Guide &
Reference Manual to change the default scale.
o Analog: Enter values that fall within the "Scale" range you entered previously. In
our example, we entered a conversion scale of 0 to 20 (amps), and we've chosen
to generate alarms at the high and low thresholds of 6 and 1 (amps). Note that if
you decided not to enable the "Reference," "Scale" and "Units" fields in the
previous step, you must enter numbers within the range 0 to 5 (for 0-5 VDC).
6. In "Adjust," you may enter a value to increase or decrease the temperature or analog
value if the reading your sensor provides differs slightly from a known value or source.
7. For models with the "Use Alarm Profile" feature: if you have configured Alarm Profiles
in the Alarm Options screen, you may choose a profile from the drop-down menu. The
default is "Profile 1."
Accept Changes
8. Click
You may now navigate to another screen; however, if you close the web interface before
the next step, you will lose your changes.
9. Click
Save Settings
will automatically reboot and commit your changes.
AVTECH Software, Inc.
at the bottom of your screen to temporarily save your settings.
in the navigation bar to the left of your screen. Your Room Alert
Page 4 of 5
AVTECH.com