EarthLinked ACM-4272A 설치 매뉴얼 - 페이지 5
{카테고리_이름} EarthLinked ACM-4272A에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. EarthLinked ACM-4272A 11 페이지. Auxiliary cooling module
Installation – Auxiliary Cooling Module Placement
The Auxiliary Cooling Module unit is placed as shown in Figure 2 relative to other components in
®
the EarthLinked
system. The Auxiliary Cooling Module is located outdoors and will be
connected to the refrigerant line set (vapor tube) outside the building.
Figure 2. Auxiliary Cooling Module Placement in EarthLinked
Location Requirements for the Auxiliary Cooling Module:
1. Within 40 Feet of the earth loop line set. Minimize refrigerant line lengths.
2. Higher than the compressor unit.
3. No more than 20 feet higher than the earth loop manifolds.
4. With proper clearances around the unit:
• 24 inches minimum on the two sides and back (coil side)
• 36 inches minimum on the front (fan side)
ACM-22CP-IM (05/13)
®
System
Page 5