Entec LBS-751 빠른 시작 매뉴얼 - 페이지 12
{카테고리_이름} Entec LBS-751에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Entec LBS-751 12 페이지. Electronic sectionalizer control
Quick Start Guide
LBS-751 Control
Modbus Protocol Codes, continued
05h
Force Single Coil Command
Use function code 05h to set and clear a coil. Remote bit coil will track the binary state
value forced with the 05h function. State value "1" will Set remote bit coil and "0" will Clear
the coil. Refer to Control Point table for coil assignments and address.
Example 1:
Apply "Push Button Lock" with 05h function using Scada to force coil
address 27. Set Logic "1" for three seconds then clear to Logic "0" operates Button Lock
same as pressing PB1 directly on the front panel.
Bytes
05h Force Single Coil format from Master
1 byte
1 byte
2 bytes
1 byte
1 byte
2 bytes
For additional information about Modbus commands and a comprehensive data map refer to the
SEL 751 user manual Appendix E: Modbus Communications. A PDF copy is included on the
flash stick located inside the control cabinet or available online at www.selinc.com.
®
SEL
is a registered trademark of Schweitzer Engineering Laboratories, Inc. (SEL)
Field
Slave Address
Function Code (05h)
Coil Reference
Operation Code (FF=Set; 00=Clear)
Placeholder
CRC‐16
12
APPENDIX 2
www.Entec-USA.com