Allmand Nite Lite V Series 사용 설명서 - 페이지 9
{카테고리_이름} Allmand Nite Lite V Series에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Allmand Nite Lite V Series 17 페이지.
SERIAL NUMBER 39-000001 AND UP
Testing Generator output at the main circuit breaker:
● If testing the Generator output at the GFCI receptacle (Example "L"
above) shows zero or low voltage, or is conclusive, it will then be
necessary to test the generator voltage at the main circuit breaker. The
main breaker itself may also be tested for proper function during this
procedure.
● To access the main breaker, with the engine o ff , remove the four screws
holding the control panel face plate in place and carefully pull the face
plate away from the control panel box. Allow the face plate to hang from
the attached wiring. C aution Do not allow any of the terminals on the
control panel faceplate contact the control panel box or any other
metal object on the trailer.
● Set your multimeter scale to AC volts, start the engine. When the engine
has reached its full operating speed, touch one multimeter probe to the
ground stud, and the other probe to one of the top (input) terminals on the
main breaker. Repeat the test for both terminals ( see example "L" and
"M"). 120 volts +/- 10% must be measured at each terminal. If 120 volts +/-
10% is not measured at each terminal, either the generator, the generator
capacitor or the wiring from the generator to the main circuit breaker is
faulty.
Nite Lite V Series
9