Bürkert 8793 조립 지침 매뉴얼 - 페이지 4

{카테고리_이름} Bürkert 8793에 대한 조립 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Bürkert 8793 16 페이지. Position controller and process controller with ii 3g ex ec ic iic t4 gc / ii 3d ex tc iiic t135c dc approval
Bürkert 8793에 대해서도 마찬가지입니다: 조립 지침 매뉴얼 (16 페이지), 추가 지침 (12 페이지)

Bürkert 8793 조립 지침 매뉴얼
Step 2: Connect external position indicator
Gently pull the cover of the standard position indicator
out of the housing cover (see Fig. 2: ).
Close housing cover
note!
Display element may be damaged if the housing
cover is closed carelessly.
When the external position feedback is installed, ensure
that the housing cover is not shifted or damaged when
closing the display element.
When closing the housing cover, lift it slightly to pre-
vent it from touching the display element.
Place the external position indicator in the round recess
of the housing cover and press down until it engages
(see Fig. 2: ) .
Installation is now complete.
Next connect the external position feedback to the power
supply, as described in the following chapter.
english
12
8.

elecTrical connecTion

Proximity switch 1
Fig. 3:
Electrical connection
english
14
Proximity switch 2
2
1
3
4
Cover
for standard
display element
Fig. 2:
Connecting external position indicator
Pin Configu-
External circuit / signal level
ration
1
Supply
+10 V ... +30 V
10 ... 30 V
2
Switching
+10 V ... +30 V
output (NO)
Proximity
switch 1
3
GND
GND
4
Switching
+10 V ... +30 V
output
(NO)
Proximity
switch 2
Tab. 1:
Electrical connection
Type 8791, 8792, 8793
External position
indicator
Housing cover
english
13
1 10 ... 30 V
2 Open /
10 ... 30 V
3 GND
4 Open /
10 ... 30 V
english
15