ABB Comem RIS2 사용 설명서 - 페이지 11

{카테고리_이름} ABB Comem RIS2에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB Comem RIS2 12 페이지. Integrated safety device

ABB Comem RIS2 사용 설명서
TRANSFORMER COMPONENTS

4. Test

Comem RIS2 has fully passed the
type tests prescribed by both
European Standard EN 50216-3 and
by ABB internal technical standards,
which are listed as follows:
Type tests
• Pressure overload: 2.5 bar - 2 minutes - with oil at
115 °C
• Operation at extreme temperatures: at -40 °C and
120 °
• Classification of the IP 66 protection rating:
EN 60529
• Classification of ambient conditions: 4K2, 4Z2,
4B1, 4C2, 4S3, according to EN 60721-3-4
• Mechanical vibrations 4M4 (shock 250 m/sec
Time spectrum "I": 11 ms), according to EN 60721-3-4
• Gas or oil volume for contact switching at ambient
temperature and at the average working
temperature of the transformer: max. 150 cm
• Contact response time: < 0.5 seconds
• Allowed max. magnetic field value: 25 mT (no
intervention of Comem RIS2 According to
EN 50216-3
• Tightness test - 1000 hours in saline saturated
atmosphere UNI-ISO 9227-93 (NSS)
• Tightness test against UV ageing according to UNI
ISO 4892
.
Routine tests
Before shipment each piece is also subjected to the
following routine tests:
• Tightness test: 30 minutes - 1 bar - with oil at 90 °C
• Operation of thermostats
• Pressure switch operation
• Oil level switch operation
Options on request
• Pneumatic pump set / oil re-fill in altitude. Code:
1ZBG000053-SPAR.
Supply conditions
Comem RIS2 is supplied in a single sturdy carton
(dimensions: 400 mm x 200 mm x 160 mm, weight:
2.2 kg) and complete with the following accessories:
• Instruction booklet for installation and use
• Fixing kit
• Test report.
.
2
3
11