3. INSTALLATION CONSIDERATIONS: DIMENSIONS & WEIGHTS, MOUNTING & SPACING REQUIREMENTS
Dimensions in Inches (mm)
CTF-Xtra 25 (Without Fan)
CTF-Xtra 40 (With Fan)
CTF-Xtra 50 (With Fan)
3.1 (80)
0.7 (18.5)
1.3
(32)
Depth: 5.6 (143)
CTF-Xtra 25:
2.1 lbs (970 g)
CTF-Xtra 40, 50: 2.4 lbs (1,100 g)
5. GENERAL TECHNICAL DATA & SPECIFICATIONS
LOAD, FIRING, DIAGNOSTICS & RATINGS
AC 51 resistive or low inductance loads
CATEGORY OF USE
AC 55b infrared lamps
(Tab. 2 EN60947-4-3)
AC 56a: transformer loads
PA - Load management by adjusting the firing angle (only configuration
single-phase or delta open)
ZC - Zero Crossing with constant cycle time (settable in range 1-200sec)
BF - Burst Firing, or D.O.T. with variable cycle time optimized min.
Trigger Mode
HSC - Half Single Cycle corresponds to Burst Firing that includes ON and
OFF half-cycles.
Useful for reducing flicker with short-wave IR loads (applied only to single-
phase resistive or 3-phase 6-wire open delta loads).
V, V
2
: Voltage feedback proportional to RMS voltage value on load
(useful to compensate possible variations in line voltage).
I, I
: Current feedback: bound to RMS current value on load to compensate
2
Feedback Mode
variations in line voltage and/or variations in load impedance.
P: Power feedback: proportional to real power value on load (useful to keep
constant values of electrical power assigned regardless of load impedance
or line voltage variations).
Max rated voltage
480 Vac
Work voltage range
90 - 530 Vac
Non-repetitive voltage
1200 Vp
Rated Frequency
50/60Hz Auto-Synchronization
CTF MODEL
CTF-025
CTF-040
Rated Current, AC51 - AC55b Resistive Load
25A
40A
(@ 40˚C contin. service)
Rated current AC56A permitted trigger modes:
ZC, BF/DOT with DT (Delay Trigger), PA with
20A
32A
softstart (@ Tamb = 40 °C)
Maximum Surge Current (t = 10 ms) A
400A
520A
Maximum I
2
t for fusing (blowout) A
2
s
450
1,800
Critical dV/dt Off-state (minimum)
1,000 V/µs
Nom. Impulse Voltage
4 KV
5 KA / 480 V
Nominal SCCR
WARNING: Max. Permissable inductance loop
impedance is 500 µh
CTF-Xtra 60 (With Fan)
5 (127)
1.2 (30)
3.9
(100)
1.3
Fan
(32)
Overvoltage Protector
Depth: 5.6 (143)
Weight: 3.3 lbs (1,500 g)
FUNCTION
Detection of shorted load circuit, absence of line voltage, HB alarm (partial break
Diagnostics
of load)
OPTIONS
- Timed Soft-Start firing ramp, with or without peak current control
- Soft-Start firing ramp (specific for infrared lamps)
Options
- Timed shut-off ramp
- Limitation of RMS current in load
- 0-90° Delay-Triggering for firing inductive loads in ZC & BF/DOT modes.
- SCR in short circuit (presence of current with OFF control)
- Absence of SCR current when under load.
- Overtemperature alarm
Current read
Diagnostic
• HB alarm: interrupted or partially interrupted load
• Automatic calibration of HB alarm setpoint starting from current value in load
• Alarm for load in short circuit or overcurrent
Voltage read
• No line voltage
GENERAL DATA
Power Supply
CTF 25-60 A: 24 Vac 50-60 Hz / Vdc ± 25%, max 3 VA
Power Supply for
external fan (only for
24 Vdc ± 10%, max 200mA
CTF-120A model)
5 leds: RUN: run state of CPU
CTF-050
CTF-060
STATUS: operating state
Signals
ALARM: state of alarm output
50A
60A
DIGITAL INPUT: state of digital inputs
ON / OVER-TEMP.: state of SCR power / Alarm for overheating
Load Type
Single phase load, Independent single-phase load in open delta 3-phase load;
40A
50A
& Connection
3-phase load (star without neutral or closed triangle) w/ 2-leg control
Protection
IP20
520A
1150A
0 to 50˚C (32 to 122˚F) (Per EN 60947-4-3 § 7.1.1: Average Temperature over 24
1,800
6,600
Ambient Temp.
hour period shal not exceed 35˚C (95˚F)
Storage Temp.
-20˚C to 70˚C (-4˚F to 158˚F)
Relative Humidity
20...85% RH non-condensing
Ambient Cond. for use Indoor use, altitude up to 2000 m
Installation
DIN Rail EN50022 or panel with screws
Installation category II, pollution level 2, double isolation (only for model >120A):
Installation
- Max. temp. of air surrounding device 40°C; for temp. >40°C refer at derating
Requirements
curves
- Device type: "UL Open Type"
Minimum Spacing Requirements
Rear Panel Mounting Template
Length
Width
Model
In. (mm)
In. (mm)
CTF 25A/40A/50A
4.4 (112)
1.7 (44)
CTF 60A
4.4 (112)
4.4 (113)
6. FUSES & FUSE HOLDERS
Fuse Rating,
CTF Model
Amps
I
2
t
CTF-25
25A
390 A²s
CTF-40
50A
1,600 A²s
CTF-50
50A
1,600 A²s
CTF-60
63A
3,080 A²s
Fuse Rating,
CTF Model
Amps
I
t
2
All Models
1A
N/A
4. DERATING CURVES
CTF-025 & CTF-040
45
70
40
40
65
40
60
60
35
35
55
50
30
30
50
25
25
45
25
22.5
40
20
20
35
30
15
0
0
40
45
50
Enclosure / Ambient Temperature ˚C
W
L
I
2
t Extra Rapid Fuses
Power
Manufacturer's
Dissipation
Fuse Size
Model Code
Part No.
Part No.
6W
10x38
FWC25A10F
0024-07815
0024-12124
9.5W
22x58
FWP50A22F
0024-07816
0024-12199
9.5W
22x58
FWP50A22F
0024-07816
0024-12199
11W
22x58
FWP63A22F
0024-07817
0024-12199
Instrument Fuse
Power
Manufacturer's
Dissipaton
Fuse Size
Model Code
Part No.
Part No.
N/A
10x38
KTK-1
0024-01113
0024-12124
CTF-050 & CTF-060
60
55
50
50
45
40
40
45
50
Enclosure / Ambient Temperature ˚C
Fuse Holder
Fuse Holder
Fuse Holder
Rating (UL)
Rating (IEC)
30A@600V
32A@690V
100A@600V
125A@690V
100A@600V
125A@690V
100A@600V
125A@690V
Fuse Holder
Fuse Holder
Fuse Holder
Rating (UL)
Rating (IEC)
30A@600V
32A@690V
PK538
0037-75560
June 2016