Aquarii Zino 설치 매뉴얼 - 페이지 11

{카테고리_이름} Aquarii Zino에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aquarii Zino 11 페이지. Slope recessed

0-10V Information

Please read and understand the following information about 0-10V Wiring:
Local site wiring must utilize properly rated insulation so no spacing or separation is required regardless of circuit
conductor voltage.
The local site must utilize power limited/circuit wiring that has the required insulation rating for the maximum voltage in
any of the circuits if the power limit/branch circuit wiring comes in contact with other wiring.
Class 2 0-10V Wiring follows NEC Requirement 725.136 (D). Meaning electric light, power, and Class 1 circuits must
have a 6 mm separation from the Class 2 Wiring.
Conductors that operate at 150V, or less, to Ground must comply with the following:
The Class 2 circuits are installed using Type CL3, CL3R, or CL3P or permitted substitute cables provided these Class
3 cable conductors extending beyond the jacket are separated by a minimum of 6 mm (0.25 in.) or by a non-
conductive sleeve or non-conductive barrier from all other conductors.
There must be a minimum of 0.25 in. between line voltage and bus terminals for Class 2 installations.

TROUBLESHOOTING/CORRECTIVE ACTIONS

Troubleshooting/Corrective Action Assessments can only be performed by qualified/trained personnel. Failure to do so will void
any Aquarii Product Warranties.
SYMPTOM
No light output
Fuse blown or Circuit Breaker trips
Red LED diode illuminated on
Controller
Red + Green LED diode illuminated
on Controller
Green LED diode not illuminated on
Power Supply
If the Zino is still not functioning as required after the Troubleshooting/Corrective Actions have been performed, please contact
Aquarii Customer Service for further assistance.
POSSIBLE CAUSE
Power is off
Poor wire connection
Faulty supply switch
Shorted dim lines
Crossed wire(s) or a supply
wire has grounded out
Faulty Communication
Faulty Controller
Faulty Power Supply
Local Site Power issue
CORRECTIVE ACTION
Check if power supply is on
Check wiring connections
Test or replace supply switch
Verify no shorts in dim lines
Check wiring connections
Verify Correct Communication
Protocol
Replace the Controller
Replace Power Supply
Verify local site Power Supply is
on/running
9