INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS - CABLE TO BUS BAR
CB-9
Insert the cable into mold as shown leaving 1/4" gap
between cable and bar.
CB-12
Butt cables against bus bar as shown.
CB-27
Butt cable against bus bar as shown.
+1 (918) 627-5210 • 1-800-558-1373 • WWW.THERMOWELD.COM
ELECTRICAL GROUNDING • CATHODIC PROTECTION • ELECTRIC UTILITY • RAIL
®
The Contractors Choice
CB-11
Insert bar up into mold 1 3/8". Insert cable into mold allowing
1/4" gap between cable and bar.
CB-20/CB-21
Butt cable against bus bar as shown.