Aquatech Pressmain MG-LT 사용 설명서 - 페이지 3
{카테고리_이름} Aquatech Pressmain MG-LT에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Aquatech Pressmain MG-LT 20 페이지. Tankmatic tank level/temperature monitoring/control unit with smart relay control
These instructions are intended for the installer/operator/user/maintenance of this equipment
and must be kept with the equipment, for the life of the equipment and made available to all
persons. Please read GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 &
0.4 before doing anything else, and then follow them carefully.
The unit must only be installed/operated/used/maintained by a competent person; A competent
person is someone who is technically competent and familiar with safety practices and the hazards
involved.
Hydraulic Accumulators/Expansion Vessels installed as part of/in conjunction with this equipment,
with Pressure x Volume above 250 Bar‐litres, require regular formal inspection by a competent
person. This is a Legal Requirement under the "Pressure Systems Safety Regulations" (PSSR) and
the Owner/User should be made aware of their responsibility for this. (see section 3. Servicing).
Failure to install/operate/use/maintain the equipment as recommended below could cause
damage to the equipment any anything subsequently connected to it, and invalidate the warranty
provided by AquaTech‐Pressmain to the buyer.
Any damage caused to the equipment by misapplication, mishandling or misuse could lead to risk
of Electrocution, Burns, Fire, Flooding or injury to people or property dependent upon the
circumstances involved.
This equipment MAY contain moving/rotating parts that must remain guarded. Removal of or
missing guards could lead to serious personal injury.
This equipment automatically restarts after a power interruption.
We accept no responsibility or liability for any consequences or damage/losses due to
misapplication, mishandling or misuse of the equipment.
It should be noted that the assembly of pressure equipment on site under the responsibility of the
user (or his representative) is not subject to the Pressure Equipment Directive 97/23/EC. (National
legislation covering assembly on site will apply)
The latest version of this instruction manual with up to date safety information can be downloaded
from our website at www.aquatechpressmain.co.uk
0.1
WARNINGS
0.1.1
Do not touch any live parts for at least 5 minutes after switching off the electricity supply. Failure to
observe this will constitute a severe Electric shock and/or Burns hazard and may be lethal.
0.1.2
The equipment is only suitable for earth referenced supplies and must be permanently earthed to
avoid Electric shock hazard.
0.1.3
With equipment isolator OFF, mains voltage may still be present from BMS system. This constitutes
an Electric shock hazard.
0.1.4
Emergency stop button does not remove dangerous voltages from control panel/pump motor
assemblies. This constitutes an Electric shock hazard.
0.1.5
Metal parts (e.g. heat sinks) may reach temperatures of 90 degrees centigrade and will constitute a
Burns hazard.
0.1.6
Some equipment is designed to operate with liquid temperatures up to 150 degrees centigrade and
will constitute a Burns/scalding hazard.
Aquatech‐Pressmain Instruction manual\Tankmatic smart relay MG‐LT
0. GENERAL SAFETY INFORMATION
Tankmatic Smart Relay
3