Heat Pump Placement & Clearances
2" THREADED MALE
PIPING CONNECTIONS
WATER IN-OUT PORT
INDICATOR LABEL
1. To allow for proper condensation drain-
age, use a level slab to elevate the heat pump
to at least the same height as the pool filter
system slab or 2 to 3 inches "minimum" above
grade.
2. Allow the minimum air flow clearances
on top and the sides as shown here. Make
sure the unit can "breathe" well. Do not in-
stall indoors or where the discharge air can
accumulate and be drawn back through the
heater. Make sure the front is accessible
for future service.
3. Keep sprinkler heads at least 6 feet away
from the heat pump. Do not allow the sprin-
kler to spray the unit in any way to prevent
damage.
4. If the unit is installed under a sharp roof
pitch or under a roof valley without a gutter,
a gutter or diverter should be fitted to pre-
vent excessive water from rushing through the
unit.
5. Keep all plants and shrubs trimmed away
from the heater to the minimum clearances
shown here to prevent air coil damage.
6. If the heater is installed above or below
the pool water level by more than 3 feet you
may require an external water flow switch.
See the bottom of page 7 for more informa-
tion.
FAN DISCHARGE
AIR FLOW OUT
Minimum Air Flow
& Access Clearances
Page 4