Alpha Group OutBack Power EnergyCell PLC Series 소유자 매뉴얼 - 페이지 6

{카테고리_이름} Alpha Group OutBack Power EnergyCell PLC Series에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Alpha Group OutBack Power EnergyCell PLC Series 20 페이지.

Alpha Group OutBack Power EnergyCell PLC Series 소유자 매뉴얼
Installation and Operation

Materials Required

Tools (use insulated tools only)
o
Digital voltmeter
o
Socket wrench
o
Torque wrench calibrated in inch-pounds
o
Box end wrench
o
Battery lifting equipment (handles) and fork lift to lift pallets of batteries
o
Rubber gloves
o
Full face shield
o
Plastic apron
o
Portable eyewash
o
Spill kit
o
Fire extinguisher (class C)
Accessories
o
Interconnect bar (included)
o
Terminal cover (included)
o
Hardware (included)
o
Interconnect cables as needed

Storage and Environment Requirements

Temperatures

o
To achieve maximum life of EnergyCell batteries, it is recommended not to operate them in
average ambient temperatures outside the range of 68°F to 86°F (20°C to 30°C). High operating
temperatures will shorten a battery's life (see page 7).
o
Do not allow batteries to freeze, as this will damage them and could result in leakage.
o
Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
o
Batteries should be stored in a cool, dry location. The best storage temperature is 77°F (25°C), but
a range of –4°F to 104°F (–20°C to 40°C) is acceptable.
6
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable ampacity
must meet the needs of the system, including temperature, deratings, and any other
code concerns.
900-0227-01-00 Rev A