Alpha IP FAL 21001-06 매뉴얼 - 페이지 13

{카테고리_이름} Alpha IP FAL 21001-06에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Alpha IP FAL 21001-06 17 페이지.

The configuration menu for the Alpha IP base station includes device parameters "UnP1/UnP2" and
channel parameters "ChAn", allowing to change lead and follow-up times for the pump, setback temper-
atures, time intervals and many other parameters. The following table shows the available parameters:
UnP1:
Parameters
Antifreeze temperature
Pump control
Load equilibration:
Heating zones will be con-
trolled in a staggered way if
possible
Load collection:
Heating
zones
controlled collectively.
Actuator
NC - Normally Closed
NO - Normally Open
*If heating zone 1 is used as
pump control, it is necessary to
teach in a wall thermostat to
this heating zone, if an adap-
tation of the pump parameters
shall be performed.
Emergency operation
in heating mode
Emergency operation
in heating mode
Index
Value
P024
3
4
5
...
16 (default)
...
19
20
P025
0
1
2
are
3
types:
4 (default)
5
6
7
P026
0
1
...
25 (default)
...
99
100
P032
0 (default)
1
...
99
100
Meaning
Antifreeze protection inactive
2.0 °C
2.5 °C
...
8.0 °C
...
9.5 °C
10.0 °C
active,
with
load
actuator type NC
active, with load equilibration
actuator type NO
active, with load collection
actuator type NC
active, with load collection
actuator type NO
inactive, with load equilibration
actuator type NC
inactive, with load equilibration
actuator type NO
inactive, with load collection
actuator type NC
inactive, with load collection
actuator type NO
0 %
1 %
...
25 %
...
99 %
100 %
0 %
1 %
...
99 %
100 %
Configuration
equilibration,
13