Dictator RZ-24 기술 매뉴얼 - 페이지 17
{카테고리_이름} Dictator RZ-24에 대한 기술 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Dictator RZ-24 19 페이지. Central
7a) Steps for Placing into
Operation
7b) Functional Tests,
Approval
Ill. 11
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
7. Placing into Operation of the Hold-Open System
- After having connected all components in the RZ-24 central, close the
cover and secure it with the 4 screws.
- Switch on the voltage supply.
When everything has been connected
correctly =>
the horn in the casing will sound,
the red LED (1) on the cover will be
on.
- Reset the fire detection line by
pressing the key RESET (2) on the
cover. The horn will be switched off.
Now the system is ready for
operation.
When the system is ready for operation, its correct functioning and its
installation according to the regulations has to be stated by an approval
test. Only a correspondingly trained and authorized professional may
effect this approval test.
Extent of the approval test
- Checking whether all installed devices are included in the approval of
the RZ-24.
- Verifying whether the labelling of the installed devices corresponds to
the labelling specified in the approval of the building authorities.
- Checking the interaction of all devices: Tripping by simulating the fire
parameter on which is based the functioning principle of the detectors
(e.g. smoke detectors by aerosol) as well as manually (pressing the
hand release switch on the central and the ones installed beside the
door).
- Checking whether the closure (door etc.) is also released for the
automatic closing if the hold-open system doesn't work (e.g. due to a
power cut or a defect detector, to be simulated by removing a detector
and cutting the 230 V supply of the RZ-24 central).
After the successful approval test, the operating company has to perma-
nently fix a plate of 105 mm x 52 mm in the immediate vicinity of the
closure which has to be provided by the manufacturer of the hold-open
system and reads
Type approval no. Z-6.500–2443
Company logo
Hold-open system
Approved by
month/year
Technical Manual
RZ-24 Central
(2)
(3)
(1)
Ill. 10
Page 07.021.17