HUIZHOU EPEVER TECHNOLOGY CO., LTD.
7. Protection
Protection
Conditions
The PV can be reversely connected with a
controller when:
✓ Only the PV is connected with the
PV Reverse
controller;
✓ The battery is positively connected.
Polarity
The PV's open-circuit voltage is lower
than 85V(This requirement is only for
Tracer26/39/5210BPL).
When the PV is not connecting or the
connection reversed, the battery can be
Battery
reversed.
Reverse
WARNING: Controller will be damaged
Polarity
when the PV connection is correct, and
battery connection reversed!
Battery Over
The battery voltage reaches the OVD
Voltage
Battery Over
The battery voltage reaches the LVD
Discharge
The temperature sensor is higher than 65℃
Battery
Overheating
The temperature sensor is less than 55℃
The temperature sensor is less than the
Lithium battery
low-temperature value(Default 0℃)
Low
The temperature sensor is higher than the
Temperature
low-temperature value(Default 0℃)
Load current ≥2.5 times rated current
One short circuit, the output is OFF 5s;
Two short circuits, the output is OFF 10s;
Load Short
Three short circuits, the output is OFF 15s;
Circuit
Four short circuits, the output is OFF 20s;
Five short circuits, the output is OFF 25s;
Six short circuits, the output is OFF
Lithium battery
Limit current temperature
limit current in
T1>T2>T3>T4>T5>T6
low
Limit current I1>I2>I3>I4>I5>I6
temperature
8. Technical Specifications
Item
Nominal system voltage
Battery input voltage range
Rated charge current
Rated charge power
Max. PV open circuit voltage
MPP Voltage range
Max. output current
Max. output power
Output voltage range
Load open circuit voltage
Load over voltage protection
Maximum output efficiency
Output current control accuracy
Battery Type
Equalize Charging Voltage
Boost Charging Voltage
Float Charging Voltage
Low Voltage Reconnect Voltage
Low Voltage Disconnect Voltage
Boost Charging Voltage
Low Voltage Reconnect Voltage
Low Voltage Disconnect Voltage
Self-consumption
Temperature compensation coefficient
Communication
Working environment temperature
Enclosure
Dimension
Mounting hole size
Mounting size
Power cable
Net weight
The controller has the charge current limit function. The charge current can be set via the APP software and the remote controller.
The Max. output power is the same for either the 12V or 24V system, shown above the table.
Status
The controller is no damage
Stop charging
stop discharging
Output is OFF
Output is ON
Lithium battery stop
charging/discharging
Lithium battery charging
Output is OFF
Clear the fault: Restart the
controller or wait for one
night-day cycle (night
time>3 hours).
When the temperature is
lower than T1, the charging
current is I1; when the
temperature is lower than
T2, the charging current is
I2; and so on. However,
when the temperature rises
gradually from T4 to T1, it is
performed at I4.
Tracer2606BPL
Tracer3906BPL
12/24VDC Auto(Lithium battery do not automatically identify system voltage)
10A
15A
130W/12V;260W/24V 200W/12V;400W/24V 260W/12V;520W/24V 130W/12V;260W/24V
60V( at minimum operating environment temperature )
46V( at 25℃ environment temperature )
( Battery voltage+2V)~36V
3.3A
4.5A
100W
130W
Lead-acid battery: Sealed(Default) / Gel / Flooded/User; Lithium battery:LiFePO4/ Li-NiCoMn/User
-3mV/℃/2V(Lithium battery don't have temperature compensation coefficient)
124×89×30mm
150×93.5×32.7mm
88×76mm
120×83mm
2
PV/BAT:14AWG(2.5mm
)
2
LOAD:18AWG(1.0mm
)
0.54kg
0.73kg
3
Tel:+86-10-82894896/82894112/+86-752-3889706
9. Troubleshooting
Faults
LED Charging
indicator turn off
during daytime
PV
when sunshine
array disconnection
falls on PV
modules properly
Battery voltage may be
No LED indicator
less than 9V
Battery LED
indicator green
Battery over voltage
fast Flashing
Battery
Battery LED
indicator red
over discharged
Battery LED
indicator red
Battery Overheating
flashing
①The connecting wires
are error or
virtually connected
Powering on
②Load mode is not
normally, the load
appropriate.
is off
③This controller does not
match the LED light.
④Output short circuit.
The controller does not
match the LED light
source. This product is
The dimming
step-up voltage control. If
function is invalid
the input voltage is lower
than the rated voltage, it
is not working.
①After the battery is over-discharged, the battery indicator is red. And the load is turned
off all the time until the voltage reaches the Low Voltage Reconnect Voltage (LVRV). To
judge the system is normal or not, firstly measuring whether the battery voltage is higher
than LVRV. If not, restarting the controller to detect whether the load output is normal.
NOTE: The LVRV can be set, but it must pay more attention to modification. Too
low LVLR may damage the battery.
10. Disclaimer
This warranty does not apply under the following conditions:
Damage from improper use or use in an unsuitable environment.
PV or load current, voltage, or power exceeds the controller's rated value.
The controller's working temperature exceeds the limit working environment
temperature.
User disassembly or attempted to repair the controller without permission.
The controller is damaged due to natural elements such as lighting.
The controller is damaged during transportation and shipment.
Tracer5206BPL
Tracer2610BPL
9~32VDC
20A
100V( at minimum operating environment temperature )
6.6A
3.3A
200W
100W
( Max. battery voltage+2V)~58V
58V
63V
96%
≤2%
Sealed :14.6V/Gel:No / Flooded:14.8V/User:9-17V (×2/24V)
Sealed :14.4V/Gel:14.2V/Flooded:14.6V/User:9-17V (×2/24V)
Sealed/Gel/Flooded:13.8V/User:9-17V (×2/24V)
Sealed/Gel/Flooded:12.6V/User:9-17V (×2/24V)
Sealed/Gel/Flooded:11.1V/User:9-17V (×2/24V)
LiFePO4:14.5V/ Li-NiCoMn:12.5V / User:9-17V (×2/24V)
LiFePO4:12.8V / Li-NiCoMn:10.5V / User:9-17V (×2/24V)
LiFePO4:11.1V / Li-NiCoMn:9.3V / User:9-17V (×2/24V)
≤15mA/12V;≤22mA/24V
RS485
-40℃~+60℃
IP67
153×105×52.1mm
124×89×30mm
Φ3.5mm
120×94mm
88×76mm
PV/BAT:12AWG(4mm
2
)
LOAD:16AWG(1.5mm
2
)
1.18kg
0.54kg
Possible reasons
Confirm that PV and battery wire
connections are correct and tight
Measure battery voltage with the
multi-meter. Min.9V can start up the
controller
Check if the battery voltage is higher
than OVD, and disconnect the PV
When the battery voltage is restored
to or above the LVR point (low
①
voltage reconnect voltage), the load
will recover
The controller will automatically turn
the system off. But while the
temperature decline to be below 50
ºC, the controller will resume.
① Check the connecting cable.
② Check the load's mode and
parameters.
③The voltage of LED light is not
within the output voltage range of
the controller.
④Check the connecting cables and
LED light.
①Replace the LED light
②Reduce system rated voltage
grade, and replace the product
model
For example 24V system change to
a 12V system and replace the
corresponding controller
Tracer3910BPL
10A
15A
200W/12V;400W/24V
92V( at 25℃ environment temperature )
( Battery voltage+2V)~72V
4.5A
130W
150×93.5×32.7mm
120×83mm
2
PV/BAT:14AWG(2.5mm
)
2
LOAD:18AWG(1.0mm
)
0.73kg
4
Website:www.epever.com
Troubleshooting
Tracer5210BPL
20A
260W/12V;520W/24V
6.6A
200W
153×105×52.1mm
120×94mm
PV/BAT:12AWG(4mm
2
)
LOAD:16AWG(1.5mm
2
)
1.18kg