For XM3 units in service, backup battery power will not be available during this procedure.
Before removing the Inverter Module, verify the power supply device address is correct.
The power supply device address must not be set to zero and no two power supplies monitored by a single DM3 Series Transponder can have the same address. Power supplies must have 1, 2, 3, 4 or 5 as an
address.
To verify the power supply's address, go to the LCD display on the inverter module and enter the "PWR CNFG" menu. Scroll to the "Device Address" menu item and verify the device address is set to something
other than 0 (Zero).
If power supply data will not display.

Removing the Inverter Module:

Service personnel must verify the Inverter Module battery breaker remains in the OFF position until instructed to return the unit to service.