2. General information about UniSec Digital
The UniSec Digital monitoring system can be
configured with the following components:
• Concentrator MDC4-M
• Wireless temperature sensors
• Environmental sensor (optional)
• Gas pressure sensor (optional)
Each sensor is connected via cable or in the wireless
mode (in the case of temperature sensors) to the
concentrator, which collects all the data measured
and transmits them to the user via LHMI module or
mobile APP.
Typically, 3 wireless sensors are installed in the main
circuit of the digital units (cable connection
monitoring), but up to 9 can be installed if
monitoring relating to circuit-breakers and busbars
is required.
Temperature sensor
SF
pressure
6
The sensors installed in the switchgear enable the
following operating parameters to be monitored:
• Temperature of the main circuit (the monitoring
points depend on how the switchgear has been
configured)
• Temperature and humidity levels in the cable
compartment
• ressure of gas in GSec/HySec apparatuses
NOTE
The sensors in the monitoring system do
not need to be calibrated
Ambient T/Humidity
Local HMI