ABB ACS355 series 보충 설명서 - 페이지 2
{카테고리_이름} ABB ACS355 series에 대한 보충 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACS355 series 16 페이지. Variable frequency drives in renewaire ventilators
ABB ACS355 series에 대해서도 마찬가지입니다: 보충 설명서 (20 페이지), 빠른 설치 및 시작 매뉴얼 (2 페이지), 빠른 설치 및 시작 매뉴얼 (2 페이지), 설치 지침 (4 페이지), 빠른 설치 및 시작 매뉴얼 (4 페이지), 설치 지침 (4 페이지)
PRODUCT INFO
ABOUT ABB VFDS
PLANNING
YOUR INSTALLATION
2
RENEWAIRE.COM
ABB VFD SUPPLEMENTAL MANUAL
ABB VARIABLE FREQUENCY DRIVES
ABB ACS320 VFDs are generally supplied in indoor ERVs and ABB ACS355+N831 VFDs in roof top ERVs.
Both models have built in BACnet
low ambient fi rmware that extends the lower starting temperature limit to -25°F.
FOR COMPLETE ERV INSTALLATION YOU WILL ALSO NEED:
• Standard Installation and Operation Manual for the ERV – physical installation and duct connection,
maintenance procedures, etc.
• Supplemental Wiring Schematic Manual – complete unit wiring diagrams.
• User's Manual ACS320 Drives or Users Manual ACS355 Drives – ABB's user's/installer's manual.
More detailed information is available online in the Document Library at www.abb.com/drives.
RISK OF FIRE, ELECTRIC SHOCK, OR INJURY. OBSERVE ALL CODES AND THE FOLLOWING:
1. Before servicing or cleaning the unit, switch
power off at disconnect switch or service panel
and lock-out/tag-out to prevent power from
being switched on accidentally. More than one
disconnect switch may be required to
de-energize the equipment for servicing.
2. This installation manual shows the suggested
installation method. Additional measures may
be required by local codes and standards.
3. Installation work and electrical wiring must be
done by qualifi ed professional(s) in accordance
with all applicable codes, standards and
licensing requirements.
4. Any structural alterations necessary for
installation must comply with all applicable
building, health, and safety code requirements.
NOTE: VFD(s) in this unit can be operated in many ways. This Manual provides only an outline of common methods.
DO NOT OPERATE VFD IN CONDITIONS OUTSIDE OF TEMPERATURE LIMITS. The manufacturer's normal
ambient temperature limits for ACS320 VFDs are 14°F to 122°F. RenewAire has worked with the manufacturer
to implement low-ambient-start fi rmware for the ACS355+N831 that extends the lower temperature
limit for starting the VFD down to -25°F, which has been validated by manufacturer and RenewAire testing.
The manufacturer recommends that the VFD not be operated for prolonged periods at temperatures below
14°F to ensure longevity of the VFD. RenewAire commercial ERVs are VFD ready, in extreme climates
consider fi eld installing VFDs in a climate controlled indoor electrical cabinet.
1.800.627.4499
®
building communication protocol and the ACS355+N831 also has
WARNING
5. This unit must be grounded.
6. Use the unit only in the manner intended by the
manufacturer. If you have questions, contact
the manufacturer.
7. When cutting or drilling into unit, wall or
ceiling, do not damage electrical wiring and
other hidden utilities.
8. Do not re-wire the VFD(s) to control more than
one motor per VFD.
9. Do not operate the motors in this unit above
the motor's rated full load amps (FLA) as
indicated on the unit's nameplate.
WARNING