ABB ACS850-04 series 빠른 설치 매뉴얼 - 페이지 5
{카테고리_이름} ABB ACS850-04 series에 대한 빠른 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACS850-04 series 16 페이지. Converter modules with electrolytic dc capacitors in the dc link
ABB ACS850-04 series에 대해서도 마찬가지입니다: 매뉴얼 (16 페이지)
Frame size E: Screw terminal installation (95 to
2
240 mm
[AWG3/0 to 500MCM] cables)
U1
V1
W1
R-
8 N·m (5.9 lbf·ft)
Input power cable
UDC+
R+ UDC-
U2
V2
PE
Motor cable
a
b
W2
a. Connect the cable to the terminal. Tighten the
Allen screw to 20...40 N·m (15...30 lbf·ft).
b. Connect the terminal to the drive. Tighten to
30...44 N·m (22...32 lbf·ft).
Wire sizes accepted by power
terminals
Drive type ACS850-04...
-103A-5, -144A-5
-166A-5...-290A-5
Tightening torques
Drive type
ACS850-04...
-103A-5, -144A-5
-166A-5...-290A-5
Quick installation guide – ACS850-04
WARNING! If the wire size is less than
2
95 mm
(3/0 AWG), a crimp lug must
be used. A cable of wire size less than
2
95 mm
(3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
Wire size
6 ... 70 mm
95 ... 240 mm
Power terminals
N·m (lbf·ft)
15 (11)
Cable lug installation
30...44 (22...32)
Allen screw
20...40 (15...30)
Screw terminal installation
30...44 (22...32)
5
2
2
PE
N·m (lbf·ft)
15 (11)
8 (5.9)
8 (5.9)