The actuator only requires the basic settings (adaptation to the operating range) in order to be oper-
ated with the standard or custumer specific configuration. Use the Local Control Panel (LCP) for these
settings. Use the appropriate configuration software for more detailed parameter changes or diagno-
sis functions.
9.1
Set-up via local control panel (LCP)
9.1.1
Operating elements
IMPORTANT 1. Write-protect switch
2. LED for 100% position
3. Drive buttons
4. Reset button
5. Power LED
6. RS 232 socket
7. Potential toggle switch
8. LED for 0% position
9. Accept button (0%)
10. Accept button (100%)
Fig. 12:
Local Control Panel (LCP)
WARNING
The actuator operating range is not preset when it leaves the factory!
9.1.2 Setup procedure
- Undo the screws of the LCP cover
- Swing the cover to the side
9.1.3 Initial situation
- Electronics connected to power supply and actuator
- Write-protect switch (1) set to "OFF" position
- Electronics in operating mode "MAN" (no signal on DI 1)
- No fault (if a fault occurs, both LEDs flash alternately at 4 Hz)
A68-2005-003 EN
Electrical Part Turn Actuators for Continuous Modulating Control PME120AI (Contrac)
(Default setting: OFF)
Indication if adjustment procedure, saved position, or fault by differ-
ent flash frequencies.
Press to cause drive motion
Press to restart processor
Indicates available mains supply
Connection socket to PC
Connection of reference potential to the system or protective earth
(by default set to system) of electronic unit
Indication if adjustment procedure, saved position, or fault by differ-
ent flash frequencies..
Press to define current position as 0%; simultaneously press push
button 9 + 10 to complete the adjustment procedure.
Press to define current position as 100%; simultaneously press push
button 9 + 10 to complete the adjustment procedure
5
10
4
9
8
1
Setup
2
3
7
6
(r0110rxa)
15