Digidim 505 사용자 설명서 - 페이지 12
{카테고리_이름} Digidim 505에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Digidim 505 16 페이지. Av interface package
Digidim 503AV / 505 RS232 AV Interface User Guide
7.3. Message List
Note:
Refer to document 7860077, 'RS232 to DALI Command List' for a full list of DALI commands.
Command
Set Interface AV mode – this command must be sent at
power up.
General form
Go to level 'dd'
OFF
UP
DOWN
STEP UP
STEP DOWN
Recall MAX level
Recall MIN level
STEP DOWN and OFF
ON and STEP UP
Doc. No. 7860076
Transmit
03, 82, 02, 00
No. of bytes to follow, type, DALI address, DALI command or
data
03, 51, a0, dd
where a0 = {bxxxxxxx0}DALI level address and
dd = DALI level of 00 through FE
03, 51, a1, 00 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 01 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 02 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 03 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 04 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 05 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 06 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 07 where a1 = {bxxxxxxx1}DALI command
address
03, 51, a1, 08 where a1 = {bxxxxxxx1}DALI command
address
Page 10
Helvar Ltd
Return
03, 82, xx, yy
where the decimal value
of xx.yy is the Interface revision
No. of bytes to follow, reply type (see notes),
returned data or message echo
03, 64, a0, dd
03, 64, a1, 00
03, 64, a1, 01
03, 64, a1, 02
03, 64, a1, 03
03, 64, a1, 04
03, 64, a1, 05
03, 64, a1, 06
03, 64, a1, 07
03, 64, a1, 08
Issue 8