Pin Terminal
Crimp Tool
• Accompanying AC type power supply
plug is CA7-ACCNL-01 from Pro-face or
FKC2.5/3-STF-5.08 is manufactured by
Phoenix Contact.
• Accompanying DC type power supply
plug is CA7-DCCNL-01 from Pro-face or
GFKC2.5/3-STF-7.62 is manufactured by
Phoenix Contact.

Connecting the Power Cord

(1) Confirm that the power is not supplied to
the PS-A unit.
(2) Push the Opening button with a small and
flat screw driver to open the desired pin
hole.
(3) Insert each pin terminal into its each hole.
Release the Opening button to clamp the
pin in place.
AC power supply cord
Green/Yellow
DC power supply cord
(4) After inserting all three pins, insert the
Power Plug into the Power Connector at
PS-A. Fix the plug with two (2) slot
screws.
• Confirm that all wires are connected
correctly.
• The torque required to tighten these
screws is 0.5 to 0.6N•m.
CRIMPFOX ZA3
(1201882)
Opening Button
L
Black
N
White
FG
Opening Button
• To prevent the possibility of a terminal
short, use a pin terminal that has an
insulating sleeve.
1.

Power Supply Cautions

• Input and Output signal lines must be
separated from the power control cables
for operational circuits.
• To improve the noise resistance, be sure to
twist the ends of the power cord wires
before connecting them to the Power Plug.
• The PS-A unit's power supply cord should
not be bundled with or kept close to main
circuit lines (high voltage, high current), or
input/output signal lines.
• To reduce noise, make the power cord as
short as possible.
• If the supplied voltage exceeds the PS-A
unit's range, connect a voltage transformer.
• Between the line and the ground, be sure to
use a low noise power supply. If there is an
excess amount of noise, connect a noise
reducing transformer.
• The temperature rating of field installed
conductors: 75°C only.
• Use voltage and noise reducing
transformers with capacities exceeding
Power Consumption value.
• Connect a surge absorber to handle power
surges.
• Be sure to ground the surge absorber
(E1) separately from the PS-A unit
(E2). Select a surge absorber that has
a maximum circuit voltage greater than
that of the peak voltage of the power
supply.
E1
13
PS-A
FG
E2
Lightning Surge Absorber