Chapter 6
System Components
Removing Data Rail From Panel
1. Disconnect and lock off all
power sources supplying this
panel.
2. Remove panel trim and deadfront.
3. Loosen the screw (2 total) that
secures the data rail lid as shown
in figure 6.14 to open the lid for
CPOD and ribbon cable
connections access.
4. Disconnect/unplug all of CPOD
connectors from data rail
connector.
5. Disconnect/unplug the ribbon
cable from the ribbon connector.
6. Loosen and uninstall the screw
(4 total) from the data rail
mounting bracket and panel
deadfront support bracket
Neutral Extension
Description
The neutral extension is an adapter
piece that mounts to the neutral of
the panel. This device allows the user
to gain additional low amperage
neutral connections when the CPODs
partially cover the normal neutrals.
The neutral extension provides
connection for 18 wires ranging from
#6-#14 AWG and 3 wires ranging
from 1/0-#14 AWG (21 connections
in total).
Figure 6.15
Left Neutral Extension for
Bottom-feed Panel
Figure 6.16
Right Neutral Extension for
Bottom-feed Panel
23