Wire Connector
[ Conexión
del cable ]
5 mm
OR
3/16"
TW1FG350 / 3VL9335-4TC01
3TW1FG350 / 3VL9335-4TC31
4TW1FG350 / 3VL9335-4TC41
*)
Attention!
EN
Ensure when connecting that the wire is in the center and avoid any misalignment of the holding plate.
Atención
ES
Al conectar atender a que el conductor quede centrado y evite que la chapita de retención quede ladeada.
Important !
FR
Lors du serrage, veiller à ce que le conducteur soit bien placé au milieu de la cage et que la plaquette de serrage soit droite.
Technical Support: Internet:
Subject to change without prior notice. Store for use at a later date.
Sujeto a cambios sin previo aviso. Guardar para futuro uso.
UL 486A - 486B
Req. Wire Stranding
Wire Size
[ Rango Cable ]
CU / AL
Class B
Cu Only
3 – 1 AWG
7 STRANDS
[ 35 mm² ]
Cu Only
1/0 – 4/0 AWG
7 STRANDS
[ 70 -95 mm² ]
Cu Only
37 STRANDS
250 kcmil
[ 120 mm² ]
http://www.siemens.com/lowvoltage/technical-support
( Cable )
[ esfuerzo de torsión ]
CU
Class C
19 STRANDS
19 STRANDS
61 STRANDS
Order No. / Referencia: 3ZX1012-0VL68-5AA2
Wire
Strip
Torque
Length
[ Quitar ]
A
220 lb. in. *)
.87"
[ 25 Nm ]
[ 22 mm ]
GWA 4NEB 179 6872-10 DS 04