Table 5- 6
Diagnostics
alarm
Short-circuit
High limit violat-
ed
Low limit violated 8
Error
Parameter error
Hardware inter-
rupt lost
Table 5- 7
Diagnostics
alarm
Wire break
High limit violat-
ed
Parameter error
Hardware inter-
rupt lost
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Manual, 08/2018, A5E32350124-AD
Diagnostics alarms - for the measuring range: 0 V to 10 V and 4-DMU 0 mA to 20 mA
Error code
Meaning
1
Short-circuit encoder supply to
H
ground
7
Value is above overrange.
H
Value is below underrange.
H
9
Value is significantly above or
H
below underrange/overrange.
10
Module parameter assignment is
H
faulty
16
At least one hardware interrupt
H
could not be signaled because
too many hardware interrupts are
pending.
Diagnostics alarms - for the measuring range: 150 Ω and 300 Ω
Error code
Meaning
6
Impedance of encoder circuit too
H
high
Wire break between the module
and sensor
Channel not connected (open)
7
Value is above overrange.
H
10
Module parameter assignment is
H
faulty
16
At least one hardware interrupt
H
could not be signaled because
too many hardware interrupts are
pending.
Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Remedy
Correct interplay between module
and encoder
Correct interplay between module
and sensor
Correct interplay between module
and sensor
Correct interplay between module
and sensor
Correct the parameter assign-
ment
Correct the program or the pro-
cess
Remedy
Use a different encoder type or
modify the wiring, for example,
using cables with larger cross-
section
Connect the cable
Deactivate diagnostics
Connect the channel
Deactivate channel
Correct interplay between mod-
ule and sensor
Correct the parameter assign-
ment
Correct the program or the pro-
cess
35