Siemens SIMATIC ET 200SP HA 장비 매뉴얼 - 페이지 40

{카테고리_이름} Siemens SIMATIC ET 200SP HA에 대한 장비 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SIMATIC ET 200SP HA 42 페이지. Distributed i/o devices busadapter for distributed i/o
Siemens SIMATIC ET 200SP HA에 대해서도 마찬가지입니다: 매뉴얼 (32 페이지), 매뉴얼 (50 페이지), 매뉴얼 (34 페이지), 매뉴얼 (38 페이지), 장비 매뉴얼 (44 페이지), 장비 매뉴얼 (50 페이지), 장비 매뉴얼 (38 페이지), 장비 매뉴얼 (46 페이지), 장비 매뉴얼 (44 페이지), 장비 매뉴얼 (36 페이지), 장비 매뉴얼 (38 페이지)

Siemens SIMATIC ET 200SP HA 장비 매뉴얼
Parameters, diagnostics messages and address space
A.7 Address space of the time stamping (accuracy 1 ms)
A.6

Address space

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "DI" stands for digital input
• "QDIn" stands for the value status (QI) of digital input n
Address space
The following figures shows the assignment of the address space of the DI 8×24...125VDC HA.
IB x +
Meaning
0
DI7
DI6
1
QDI7
QDI6
Evaluating the value status
There is a bit value status for each digital input in the input address space.
Irrespective of the diagnostics enables, each value status (each QI bit) provides information on
the validity of the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" if the digital value can be detected without error. The
value status is set to "bad" in the following cases:
• The process value cannot be recorded due to an error.
• The digital channel is deactivated.
Note
The value status is not set to "bad" when there is a wire break on the channel and the wire break
test is disabled.
A.7

Address space of the time stamping (accuracy 1 ms)

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "DI" stands for digital input
• "QDIn" stands for the value status (QI) of digital input n
40
DI5
DI4
QDI5
QDI4
DI3
DI2
QDI3
QDI2
Equipment Manual, 10/2021, A5E39288633-AD
DI1
DI0
QDI1
QDI0
DI 8x24...125VDC HA