Technical specifications
Article number
Switching capacity of contacts
Cable length
Interrupts/diagnostics/status information
Diagnostics function
Diagnoses
Diagnostics indication LED
Potential separation
Potential separation channels
Permissible potential difference
between different circuits
between channels and backplane bus/supply
voltage
Isolation
tested with
Ambient conditions
Ambient temperature during operation
Altitude during operation relating to sea level
28
external protection for relay outputs
– with inductive load, max.
– with resistive load, max.
– Switching current, min.
– Rated switching voltage (DC)
– Rated switching voltage (AC)
shielded, max.
unshielded, max.
Monitoring the supply voltage
– parameterizable
MAINT LED
Monitoring of the supply voltage (PWR-LED)
Channel status display
for module diagnostics
between the channels
between the channels and backplane bus
Between the channels and load voltage L+
between channels and backplane bus/supply
voltage
between backplane bus and supply voltage
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
6DL1132-6HD50-0PK0
yes; 6 A, see data in manual
2 A; 2 A (24 V DC), 0.5 A (60 V DC), 0.1 A (120 V DC)
5 A; 5 A (30 V DC), 5 A (230 V AC)
8 mA
24 V; 24 V DC to 120 V DC
230 V; 24V AC to 230V AC
1 000 m
200 m
Yes
Yes
Yes
Yes; Yellow LED
Yes; green PWR LED
Yes; green LED
Yes; green/red DIAG LED
Yes
Yes
Yes
Between channels: 230 V AC (different system
phase)
230 V AC
4 200 V DC/1 min, type test
1 500 V DC/1 min, type test
-40 °C; No icing
70 °C
-40 °C; No icing
60 °C
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual, 07/2022, A5E39389042-AF