Product overview
2.3 Hardware properties
Properties
CPU 1513R-1 PN has the following technical properties:
Property
CPU display
Supply voltage
PROFINET IO
PROFINET IO interface
(X1 P1 R and X1 P2 R)
16
Description
All CPUs of the redundant system S7 1500R/H have a dis-
play with plain text information. The display provides you
with diagnostic messages as well as information about the
article number, the firmware version and the serial number
of the CPU.
You can also view and assign the IP addresses, the
PROFINET device name and the redundancy ID of the CPU.
The system IP address cant be viewed via STEP 7 but not in
the display.
In addition to the functions listed here, a large number of
other functions are available on the display. These addi-
tional functions are described in the SIMATIC S7 1500 Dis-
play Simulator.
The 24 V DC supply voltage is fed via a 4-pin plug located
on the front of the CPU.
The CPU has an X1 interface with two ports (X1 P1 R and
X1 P2 R).
The PROFINET IO interface X1 (default P1 R) is used to
set up the PROFINET ring with the two CPUs and the IO
devices.
The PROFINET IO interface X1 (default P2 R) is used to
make the connection between the two R-CPUs in the
PROFINET ring.
In the PROFINET ring, the synchronization frames be-
tween the CPUs are transmitted via the following con-
nections:
The direct connection (X1 P2 R)
The indirect connection (X1 P1 R) via the IO devices
The interface supports PROFINET IO RT (Real-Time) and
PROFINET basic functionality.
Basic PROFINET functionality comprises:
HMI communication
Communication with the configuration system
Communication with a higher-level network (back-
bone, router, Internet)
Communication with another machine or automa-
tion cell
Additional information
Redundant System S7-1500R/H
(https://support.industry.siemens
.com/cs/ww/en/view/109754833)
System Manual
SIMATIC S7-1500 Display Simula-
tor
(https://support.industry.siemens
.com/cs/ww/en/view/109761758)
Section Connecting (Page 25)
Redundant System S7-1500R/H
(https://support.industry.siemens
.com/cs/ww/en/view/109754833)
System Manual
Redundant System S7-1500R/H
(https://support.industry.siemens
.com/cs/ww/en/view/109754833)
System Manual
Function manual PROFINET
(https://support.industry.siemens
.com/cs/ww/en/view/49948856)
CPU 1513R-1 PN (6ES7513-1RL00-0AB0)
Equipment Manual, 05/2021, A5E42009333-AC