Product overview

3.4 Firmware functions

3.4
Firmware functions
Functions
CPU 1518HF‑4 PN supports the following firmware functions:
Function
CPU redundancy
Safety Integrated
Integrated system
diagnostics
Integrated trace
functionality
PROFINET IO
System redundancy S2
System redundancy R1
16
Description
There are two duplicate CPUs that synchronize their data
via two duplex fiber-optic cables, which connect the
CPUs directly to each other via plug-in synchronization
modules. If one of the CPUs fails, the other CPU retains
control of the process.
The integrated F-functionality processes standard and
safety programs.
This allows fail-safe data to be evaluated in the standard
user program. As a result of the integration, the system
advantages and the extensive functionality of SIMATIC
are also available for fail-safe applications.
The F-CPU is certified for use in safety mode up to:
Safety Integrity Level SIL3 acc. to IEC 61508
Performance Level (PL) e and Category 4 according to
ISO 13849-1:2006 or according to EN ISO 13849-1
Additional password protection for F-configuration and
F-program is set up for IT security.
The system automatically generates the messages for the
system diagnostics and outputs these messages via a
programming device/PC, HMI device or the integrated
display. System diagnostics information is also available
when the CPUs are in operating state STOP.
Trace functionality supports you in troubleshooting
and/or optimizing the user program.
You record device tags and evaluate the recordings with
the trace and logic analyzer function. Tags are, for
example, drive parameters or system and user tags of a
CPU.
Trace and logic analyzer functions are suitable for monit­
oring highly dynamic processes.
Note: Note that the S7-1500R/H redundant system sup­
ports recording of measurements. However, saving the
measurements to the SIMATIC memory card is not sup­
ported.
IO-Devices with S2 system redundancy enable uninter­
rupted operation during a primary backup switchover.
If the role of the CPUs changes, the new primary CPU
takes over the PROFINET IO communication.
IO devices with R1 system redundancy are equipped with
two interface modules compared to S2 devices.
If one interface module fails, the R1 device can still be
reached by the H-CPUs via the second interface module.
Thus, R1 devices have a higher availability than S2
devices.
Additional information
Redundant System S7‑1500R/H
(https://support.industry.siemens.
com/cs/ww/en/view/109754833) Sys­
tem Manual
SIMATIC Safety - Configuring and Pro­
gramming
(https://support.industry.siemens.
com/cs/ww/en/view/54110126) pro­
gramming and operating manual
Diagnostics Function Manual
(https://support.industry.siemens.
com/cs/ww/en/view/59192926)
Function manual Using the trace and
logic analyzer function
(https://support.industry.siemens.
com/cs/ww/en/view/64897128)
Redundant System S7‑1500R/H
(https://support.industry.siemens.
com/cs/ww/en/view/109754833)
System Manual
PROFINET Function Manual
(https://support.industry.siemens.
com/cs/ww/en/view/49948856)
CPU 1518HF-4 PN (6ES7518-4JP00-0AB0)
Equipment Manual, 11/2022, A5E49868646-AB