First steps for the project
2.1 Configuration of PC station
Procedure
Table 2- 1
Steps
Step Action
1
Select the "Start > SIMATIC > SIMATIC Manager" menu command or double-click on the corresponding icon on
•
the desktop. The SIMATIC Manager starts.
Select the SIMATIC PC station in the "Projects" folder of the component view.
•
Change the name of the SIMATIC PC station to the PC name.
•
In the "Properties" of the PC station, click on "Computer name identical to PC station name".
•
2
Double-click on the object "Configuration" in the right window of the SIMATIC Manager. The HW Config opens.
3
In the Hardware Catalog, open the folder
•
"SIMATIC PC Station" > "CP-PROFIBUS" > "CP 5613 A2"
Use a drag-and-drop operation to move the object "SW V6.2..." to Index 1 of the configuration table.
•
The "Properties - PROFIBUS Interface CP 5613 A2 (R0 / R1)" dialog opens.
Set the address of the PROFIBUS master, e.g. 0.
•
Select a PROFIBUS subnet.
•
Click "OK".
•
The defaults are accepted.
Notes:
A WinCC application was inserted previously by the PCS 7 wizard for creating a new project.
•
The HW Catalog may contain a newer version of the CP 5613 A2. If the PC supports this, move it to the
•
configuration table using drag-and-drop.
4
Save and compile the configuration: "Station > Save and Compile".
Make sure the result contains no errors.
12
SIRIUS Motor Starter PCS 7 Library "V7.1+SP2"/ "V8 Migration V8.0+SP1"
Getting Started, 08/2013, A5E02897539020A/RS-AA/005