3.2
Function test
3.2.1
Auxiliary voltages
Fundamentals
Tests are performed according to DIN EN 60146-1. The auxiliary voltages are visually checked
using indicator lights or using a voltmeter.
Test procedure
1. The drive power section is switched off.
2. The auxiliary voltages are switched on.
3. The auxiliary voltages are checked.
Result
The test is passed if all of the auxiliary voltages are available.
3.2.2
Interrupted cable to the operator panel
Fundamentals
An interrupted cable to the operator panel is simulated.
Test procedure
1. The drive power section is switched off.
2. The auxiliary voltage is present.
3. The interface cable between the operator panel and Control Unit is withdrawn at the
Result
The test is passed if the appropriate fault message is displayed on the operator panel.
3.2.3
DriveCLiQ connection, identification of the installed modules
Fundamentals
In automatic configuration, the installed DriveCLiQ components are detected and displayed on
the test station computer. Actual and reference state of the DriveCLiQ topology are compared.
SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11
Reference Manual Rev.201902141443 LV Umrichter
operator panel.
Tests
3.2 Function test