Siemens SITRANS LT500 적용 사례 - 페이지 16
{카테고리_이름} Siemens SITRANS LT500에 대한 적용 사례을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SITRANS LT500 24 페이지. With profibus and profinet in tia portal v16
Step 3: Setting up the device modules and process values
7. From the network view, double-click on the SITRANS LT500 connected to the PROFIBUS DP
network.
8. Just like the PROFINET module configuration, we have I and Q address assigned to the
various module process values. In our example we have inserted:
- Level module PT1
- Volume module PT1
- Sensor temperature PT1
- Relay status module
Note
To add or change the modules, you can select a different module from the Module list.
Before adding a new module, you need to delete the original module from the slot. If no
module was originally there, you delete the "No cyclic data transfer" module and then
drag the new module in from the module list into the slot.
16
SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16
Application examples, 04/2022, AG022322