3 Installation
3.1 Installation Quick Check List - Indoor MCC.s Only
Receiving
Inspect package for damage.
After unpacking, inspect equipment for damage in transit.
If damaged or incomplete, substantiate claims against
shipper with identification of parts, description of damage,
and photographs.
Handling
Simplify handling by leaving equipment on shipping skid.
Use the lifting angle provided for moving the equipment.
Take care to use the proper method of moving a motor
control center.
Storage
Store in a clean, dry space at moderate temperature.
Cover with a canvas or heavy-duty plastic cover.
If storage area is cool or damp, cover equipment completely
and heat to prevent condensation.
Location Selection
Flat and level floor.
Overhead clearance.
Accessibility front and rear (if required).
Protection from splash and drip, dust, and heat.
Space for future expansion.
If bottom conduit entry is used, conduit should be in place
and stubbed up before equipment is installed.
Installation Method
Grout into the foundation.
Weld channel sills to steel leveling plates.
Imbedded anchor bolts in the floor.
Field Assembly
(Instruction sheet included with shipment)
Remove hardware and horizontal bus connecting links from
shipping splits.
Install first shipping split.
Remove end cover plates of structures to be joined (if
required).
Carefully align second split with first. Bolt structures
together at four corners and middle, front, and rear.
Remove horizontal wireway barrier to expose horizontal
bus.
Connect horizontal buses with bus links. Torque bolts to
20 ft.-lbs.
Grommet top and bottom horizontal wireways.
Install heater coils. (Check selection against motor
nameplate data.)
Install fuses.
Conduit Entry at Top
Remove top plates from structure.
Cut conduit entry holes in top plates.
Reinstall top plates.
Install conduits
Note: This checklist is not exhaustive and particular applications my require further procedures.
Siemens Energy & Automation, Inc.
Incoming Line Connections
Choose the shortest, most direct route from remote mains.
If cables cannot be directly routed to terminals, provide
adequate space for clamping the cables.
Torque incoming lines to main lugs only at 85 ft.-lbs.
Torque all incoming connections to main circuit breakers
and fusible disconnects as per the breaker or disconnect
manufacturer's recommendations. The torque requirements
are found on a label located on the disconnecting device.
Outgoing Power and Control Wiring
Disengage plug-in unit stabs from vertical bus. Connect
control and power wiring to units.
Use stranded wire.
Leave enough slack to permit partial withdrawal of unit to
test position for maintenance.
Pull wiring between units through vertical and horizontal
wireway securing wires in the vertical wireway with wire
from wire ties provided.
Route wiring between sections through the top or bottom
horizontal wireways.
Reinsert plug-in units to engage stabs.
Pre-Operation Checks
Test insulation resistance of all circuits with the control
center as ground.
Remove restraining devices from contactors and shunts
from current transformers. Make sure that all parts of
magnetic devices operate freely.
Check electrical interlocks for proper contact operation.
Make sure that each motor is connected to its proper
starter.
Check all heater elements for proper installation.
Check all timers for proper time interval setting and contact
operation.
Check fusible disconnect starters for proper fuse size.
Clean the control center. Rid it of all extraneous material.
Use a vacuum cleaner, not compressed air.
Check all connections for mechanical and electrical
tightness
Close all access plates and doors.
Energizing Motor Control Centers
Make sure all unit disconnect handles and control
center mains are turned to OFF.
Turn on remote mains.
Turn on motor control center main circuit breakers or fusible
disconnects.
Turn on unit disconnect handles one by one.
Jog motors to check for proper rotation.
Adjust ETI Breakers.
Insulation (Megger) Test