Siemens VGD20.323U 기술 지침 - 페이지 6

{카테고리_이름} Siemens VGD20.323U에 대한 기술 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens VGD20.323U 14 페이지. Gas valves, for use with skpxx.xxxu series electro-hydraulic actuators

Siemens VGD20.323U 기술 지침
Technical Instructions 
Document Number CC1N7631us 
November 08, 2017 
 
Agency approvals/standards 
Specifications 
 
Approvals 
Operating 
Maximum operating pressure 
environment 
Maximum back pressure (differential) 
 
Close‐off pressure 
Permissible gas temperature 
Permissible operating temperature 
 
Use 
Siemens gas valves are in accordance with UL429. 
 
The valve is used as: 
Perm. mounting 
position 
 
Operating pressure 
See Type summary 
 
Types of gases 
Suitable natural gases, propane, butane and air 
 
For more information see Use. 
 
Strainer 
Built‐in, mesh size 0.9 mm 
 
Page 6 
 
 
Safety shutoff valve (in connection with SKP15.xxxU) 
Control valve with safety shutoff function (in connection with SKP25.xxxU, SKP5x.xxxU or 
SKP7x.xxxU)  
 
7631z01us/0815
UL/429, FM/7400, 
CSA/ANSI Z21.21/CSA 6.5 C / I 
IRI approvable 
Agency marks apply only for VGDxx.xxxU series 
gas valve bodies assembled with SKPxx.xxxU 
actuators. 
 
See Table 2 
VGD20.xxxU: 2 psi (150 mbar) 
VGD40.xxxU: 4 psi (300 mbar) 
See Table 2 
14 °F to 140 °F (‐10 °C to 60 °C) 
14 °F to 140 °F (‐10 °C to 60 °C) 
 
VGD Series Double Valves 