Siemens XC10 Series 운영 - 페이지 22

{카테고리_이름} Siemens XC10 Series에 대한 운영을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens XC10 Series 32 페이지. Extinguishing control unit

Siemens XC10 Series 운영

Disabling part of the system

5
Disabling part of the system
5.1

Disabling detection zones and/or manual release

22
Building Technologies
Fire Safety
In certain situations (e.g. maintenance work) it is reasonable to disable parts of the
system. If a system part is disabled (isolated), then the Led "Disabled" is lit
continuously.
Disabled system parts can under certain circumstances prevent
the correct acquisition or processing of alarms or faults as well as
WARNING
activation of extinguishing. Therefore, re-enable all disabled
system parts as soon as normal conditions prevail!
In order to prevent unintentional alarm messages or activation of extinguishing, in
exceptional cases detector zones must be isolated from the system. The instances
wherein a detector zone should be disabled depend on the detectors used and the
fault dimensions (e.g. smoke or dust).
Switched-off detector zones prevent activation of extinguishing!
WARNING
Therefore, enable all switched-off system parts again, as soon as
normal conditions prevail!
Here's how to disable a detector zone or the manual release:
1. Enable operating access level 2
2. Press key « Disable/Test/Enable » (12 to 15) next to the part to disable or test:
st
1
press: Disable (corresponding yellow Led lit up fixed),
nd
2
press: Test (corresponding yellow Led flashes slowly),
rd
3
press: Enable (corresponding yellow Led off).
When zones 1 and/or 2 are disabled or in test, yellow Led « Automatic
blocked » (16) is lit up (fixed)
When manual release is disabled or in test, yellow Led « Manual blocked » (14)
is lit up (fixed)
Disable
To disable a detection zone or the manual release whereas an alarm or a fault is
displayed, it is necessary to reset then apply the procedure above before the alarm
or fault reappears (assigned time
Test
Sequentially trigger an alarm on all the detectors / manual release buttons and
check that the red Led of the zone / manual release and the alarm indicator of the
detector / of the manual release button lights up (fixed) during
During the test, neither sound nor control is enabled.
Take care to reset the manual control button before leaving the "Test" position,
otherwise the extinguishing cycle will be triggered.
10 seconds).
10 seconds.
A6V10257477_c_en_--
2012-06