The extinguishing control unit is protected by access levels against unauthorized
manipulation.
Access level 1: operation is possible at any time.
Access level 2: operation is possible only using an access code.
In Access level 1, as a rule, only the buzzer can be silenced in the event of an
alarm or a fault. All other commands can be accessed in Access level 2.
The following block diagram shows a normal extinguishing process in the basic
setting of the control unit and with an unblocked activation of extinguishing.
Slow
Fast
Fire
Activated
alarm
Fig. 3
Block diagram process
An automatic extinguishing is enabled after the control unit has run through two
alarm levels "Fire alarm" and "Activated".
If a detector detects a fire in the extinguishing area (zone 1 or 2), it triggers a "Fire
alarm". The alarm horn sounds slow pulsating. In the case of "Fire alarm" the alarm
horn can be silenced and the system reset. The fire detectors from zone 3 monitor
as a rule the areas adjacent to the extinguishing area. Zone 3 can also be unused.