Siemens ZIC-4AC 설치 지침 매뉴얼 - 페이지 9
{카테고리_이름} Siemens ZIC-4AC에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens ZIC-4AC 12 페이지. Zone interface card
![Siemens ZIC-4AC 설치 지침 매뉴얼](/uploads/products/server2/5247693/5247693.png)
Figure 6
ZIC-4AC Single-Channel Audio Wiring
NOTES
1. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited.
3. Electrical Ratings:
Output Zone Supervisory: 4mA max @ 24VDC
Output Zone Active:
4 00 Watts max / zone
4. EOL resistor, 24k ohms, 1 watt, 5%, (comes with module package) EOL-Kit S24235-D55-A1.
5. Polarity shown in active state.
9
A24205-A334-B827
P/N 315-035850-2