Siemens SITRANS L Pointek ULS200 사용 설명서 - 페이지 21

{카테고리_이름} Siemens SITRANS L Pointek ULS200에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SITRANS L Pointek ULS200 47 페이지. Ultrasonic non-contacting switch

5.4.6

Blanking

Blanking is used to ignore the zone in front of
the transducer where false echoes are at a
level that interfere with the processing of the
true echo. It is measured outward from the
sensor face. The minimum recommended
blanking value is 0.25 m (0.82 ft) but can be
increased in order to extend the blanking.
Factory setting: 0.20 m (0.66 ft)
5.4.7

Range limit

The range limit is the distance at which measurements are ignored. Generally this refers to
the bottom of the container being measured. If a measurement is detected beyond the range
limit it results in a Loss Of Echo (LOE) reading. The result of this reading is determined by
the Fail-safe mode, see Fail-safe mode (Page 24) for more information.
Factory setting: 5.50 m (18.0 ft)
Pointek ULS200
Operating Instructions, 01/2019, A5E32268616-AB
Blanking
21