ZONE BARRELS MOUNTING INSTRUCTIONS
In the installation of zone barrels, extra caution must be taken as damper motors are IP20 Rated and MUST NOT BE
INSTALLED IN AN AREA WHERE CONDENSATION WILL BE AN ISSUE.
It is highly recommended that indoor units and accessories, particularly zone barrels, be mounted in the roof cavity. Mounting
of zone barrels should be horizontally positioned ensuring that the damper motor is located on the upper half of the barrel's
centreline (positions that range from 9 o'clock to 3 o'clock), as shown below:
Duct
TOP VIEW
Duct
SIDE VIEW
ActronAir is constantly seeking ways to improve the design of its products. Therefore, specifications are subject to change without notice.
Copyright © 2017 Actron Engineering Pty. Ltd.
Damper Motor on Top
of the Zone Barrel
Duct
Zone Barrel
PREFERRED LOCATION
Damper Motor on Top
of the Zone Barrel
Zone Barrel
Duct
RECOMMENDED LOCATION
Upper Half of Zone
Barrel's Centrline
Zone Barrel
FRONT VIEW
Damper Motor
Damper Blade
Page 11 of 20