Installation Procedures
Use a flat-head screwdriver and a counterclockwise motion to open the grounding terminal connector on
Step 5
the power terminal block. This step ensures that the correct opening is presented for the wires. (See
Figure
Figure 4-5
Correct terminal
position (open)
Step 6
Insert one end of the grounding wire into the grounding receptacle, which is the bottom receptacle in the
power terminal block connector (Callout 3 in
inserted into the terminal block so that no bare wire is exposed.
Figure 4-6
1
2
3
1
Power lead wire connection
2
Battery return wire connection
Step 7
Verify that no wire strands are left outside the connector.
Cisco 6160 Hardware Installation Guide
4-10
4-5.)
Positioning the Power and Ground Terminals to Accept Wires
Incorrect terminal
position (closed)
Inserting the Grounding and Power Wires into the Power Terminal Block Connector
PEM 1
-48/-60V
35A
, 1280VA
Chapter 4
Installing a Cisco 6160 Without a POTS Splitter Configuration
Figure
4-6). The stripped part of the wire must be fully
3
Grounding wire connection
OL-2190-02 B0