ABB ACH580-01 BxR Frame R1 사용 설명서

{카테고리_이름} ABB ACH580-01 BxR Frame R1에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACH580-01 BxR Frame R1 8 페이지.

ABB ACH580-01 BxR Frame R1 사용 설명서
ACH580-01 BxR, UL Type 1/12
Frame R1/R2
Base drive replacement instructions
Purpose or Scope
The following are the instructions for replacing an ACH580-01 UL Type 1 and 12 (Frames
R1 & R2) drive in BxR enclosures.
Equipment required*:
– Replacement drive (see note below)
– T20 bit
– T30 bit
– PZ2 bit
– PZ3 bit
– Torque wrench
– Zip ties
Basic overview of steps
– Back-up drive parameters (if you can)
– Remove power and verify after 5 minutes
– Open enclosure
– Disconnect all wiring
– Remove flange plate
– Remove drive
– Prepare replacement drive
– Remove conduit assembly
– Install in reverse order
– Check connections
– Power drive
– Reprogram and test
Notes and cautions
CAUTION! Review complete safety and electrical considerations prior
to replacing the drive. See ACH580 IOM (3AXD50000049127).
CAUTION! Two people are recommended for this job. The drive is
heavy and can fall, causing property damage and injury.
NOTE: UL Type 12 drives require a UL Type 12 replacement drive,
UL Type 1 drives are not allowed as substitutes for UL Type 12.
* Not all of these tools are needed for each frame size.