Alarm Management
If the condition does not clear, log into the Technical Support Website at
index.html
HI-TXPOWER
Default Severity: Not Alarmed (NA), Service-Affecting (SA)
Logical Object: PORT
The High Transmit Power alarm occurs when the optical power coming out of the transmit fiber is too high.
Clear the HI TXPOWER Alarm
Procedure
Step 1
Check if the correct pluggable is properly inserted.
Step 2
Check the attenuation of the input signal. See the specification details of the pluggable and set the attenuation
accordingly.
Step 3
Check if the power threshold values are set , per the recommended range. See the specification of the pluggable
and set the power threshold values accordingly.
If the condition does not clear, log into the Technical Support Website at
index.html
HOLDOVER-NOT-READY
Default Severity: Minor
Logical Object: RP
HOLDOVER-NOT-READY alarm occurs when timing source has switched and the holdover time ( i.e. 6
minutes) has not elapsed.
The alarm is expected during RP Switchovers, TE Port flap, addition or deletion or flap of BITS/SYNC-E
source.
Clear the HOLDOVER-NOT-READY Alarm
Procedure
This alarm is automatically cleared by the system when timing holdover is achieved, around 6 to 7 minutes
after timing source has switched.
Note
for more information or call Cisco TAC (1 800 553-2447).
for more information or call Cisco TAC (1 800 553-2447).
Any operation that can cause further timing switches should not be performed before this alarm is
cleared.
http://www.cisco.com/c/en/us/support/
http://www.cisco.com/c/en/us/support/
Alarms Troubleshooting Guide for Cisco NCS 4000 Series
HI-TXPOWER